Hardwired vs plug-in (NEMA 14-50) chargers
Both are correct choices. They fail in different ways, and the right pick usually comes down to amperage and where the charger lives.
The amperage ceiling
A NEMA 14-50 receptacle sits on a 50-amp circuit, and a continuous load is limited to 80 percent of that, so a plug-in charger tops out at 40 amps — about 9.6 kW. If you want 48 amps and 11.5 kW, the unit must be hardwired to a 60-amp circuit. For most drivers 40 amps is plenty; for a big-battery truck charged hard every night, the extra matters.
GFCI and the nuisance-trip problem
Current code generally requires GFCI protection for a 240-volt receptacle. Some charger and breaker combinations trip spuriously, which means walking out to a car that did not charge. A hardwired install sidesteps the issue entirely, since the charger's own internal ground-fault protection is recognized.
Outlet quality is not a detail
If you go plug-in, insist on an industrial-grade receptacle. Cheap 14-50 outlets sold for occasional RV use are a known failure point under nightly high-current charging — they overheat, discolor, and melt. The upgrade costs very little compared with the risk.
Where each one wins
Plug-in wins on flexibility: swap the unit without an electrician, take it with you when you move, and use the outlet for other 240-volt equipment. Hardwired wins outdoors and in exposed locations, where a permanent weather-sealed connection is far more durable, and it wins anywhere you want the maximum charging speed.
Either way, look for the listing mark
Buy hardware that is UL-listed or listed by another recognized testing lab, and make sure the enclosure rating matches the location. An inspector will look for it, and so will your insurer if anything ever goes wrong.